Measure ambient CO2, temperature, relative humidity, dew point, wet bulb, CO, and calculate percentage outside air.
The TPI 1010a Indoor Air Quality (IAQ) Meter is a state of the art, easy to use tester designed to provide you with the necessary measurements to monitor and make adjustments to air handling devices.
The 1010a IAQ meter uses state of the art sensors to measure carbon dioxide (CO2), and temperature.
- Calculate percent outside air to maintain acceptable CO2 levels in buildings and work spaces
- Measure and display Carbon Dioxide (CO2) and Carbon Monoxide
- Measure ambient air temperature
- Measure relative humidity, dew point and wet bulb
- Log up to 4,000 readings in 1 second to 23 hour 59 minute intervals
- Download to a computer using the A368 USB cable
- Print via I/R to optional printer (Model A740)
$995.00
USA Suggested List Price
The 1010a IAQ meter uses state of the art sensors to measure humidity, carbon dioxide (CO2), and temperature. The instrument is ruggedly constructed and comes with a 3 Year unit and 2 Year sensor Guarantee.
The TPI 1010a Indoor Air Quality meter comes complete with the following standard accessories:
• TPI 1010a Instrument
• Protective Rubber Boot (A800)
• Soft Carrying Case (A921)
• USB Cable & Software (A803)
• Instruction Manual
The TPI 1010a Indoor Air Quality meter has the following optional accessories available:
• Power adapter / Battery eliminator (A804)
• Magnetic strap kit to hang meter (A127)
• Boot hook to hang meter (A103)
• Replacement Software only (A802)
• Replacement USB cable only (A801)
Model 1010a Specifications | ||
---|---|---|
Function: CO2 | Range: 0 to 5000ppm Accuracy: 50°F~104°F: ±5% of rdg+75ppm <50°F, >104°F: ±10% of rdg+75ppm |
|
Function: Temperature | Range: -5°F to 140°F -20°C to 60°C Accuracy: ±2°F ±1°C |
|
Function: Dew Point Temperature | Range: -47°F to 135°F -44°C to 57°C Accuracy: Calculation ±1°C |
|
Function: Wet Bulb Temperature | Range: 3°F to 135°F -16°C to 57°C Accuracy: Calculation |
|
Function: Relative Humidity | Range: 5% to 95% Accuracy: ±2°F ±1°C |
|
Function: % Outside Air | Range: 0 to 100% Accuracy: Calculation |
|
Function: CO | Range: 0 to 500ppm Accuracy: ±3ppm or ±5% of rdg whichever is greater |
|
Data Logging | Up to 4,000 samples 1 sec to 23hr 59min interval | |
Display Type | 3 line with annunciators and backlight | |
CO2 Alarm | Audible and visual, selectable level (factory default 30ppm) | |
Operating Temperature & Humidity | CO and CO2: 14°F to 122°F (-10°C to 50°C) All Other Function: -4°F to 140°F (-20°C to 60°C) Humidity 15 ~ 95% non-condensing |
|
Storage Temperature | -4°F to 140°F (-20°C to 60°C) | |
Power supply | 3 AA batteries ( 4.5V) AC/DC adapter 5Vout (Center positive) Battery Life: 40 hours typical without backlight |
|
Output | Serial output via USB connection Infrared output to optional A740 printer/td> |
Model 1010a Applications
- Check ambient CO and CO2 levels in work and living spaces
- Monitor results of air control systems
- Ambient air temperature and humidity
- Test dew point and wet bulb humidity
Product Documentation